x
Send Your Inquiry Today
Quick Quote
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard front view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard right front 45deg view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard right side view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard rear view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard left rear 45deg view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard left side view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard front view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard right front 45deg view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard right side view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard rear view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard left rear 45deg view
  • 2100 kva 13.8 kv to 0.46 kv dry type distribution transformer iec standard left side view

2100 kVA Dry Type Distribution Transformer-13.8/0.46 kV | South Africa 2024

Delivery Country: South Africa 2024
Capacity: 2100kVA
Voltage: 13.8/0.46 kVA
Feature: With CT (5000/1)

2100 kVA dry type distribution transformer

Efficient 2100 kVA dry type distribution transformer with superior insulation and smart protection

01 General

1.1 Project Description

Manufactured for a South African customer in 2024, this 2100 kVA dry type distribution transformer features windings fully encapsulated in epoxy resin. Being oil-free, it lowers the risk of fire and environmental pollution. With Class F insulation rated for operating temperatures up to 155°C.

The transformer is rated at 2100 kVA, with a primary voltage of 13.8 kV and a secondary voltage of 0.468 kV (468 V). It is ideal for powering mine hoists and heavy processing equipment that operate at 468 V.

Its vector group is D(+15°)d0, where the high-voltage side features a +15° phase shift. This design meets system phase requirements and helps reduce harmonics and circulating currents during parallel operation.

The core is made of grain oriented silicon steel, which provides low losses and high magnetic flux density, contributing to a low no-load loss of 3.2 kW.

Equipped with a temperature controller and a current transformer (5000/1 CT), the transformer supports winding temperature monitoring and protection, as well as current measurement, facilitating integration into protection and monitoring systems.

1.2 Technical Specification

2100kVA Resin cast dry type transformer specification and data sheet

Delivered toSouth Africa
Year2024
TypeResin cast dry type transformer
Core materialGrain oriented silicon steel sheet
StandardIEC60076
Rated Power2100kVA
Frequency60HZ
PhaseThree
Vector groupD(+15°)d0
Cooling TypeAN
Primary Voltage13.8 KV
Secondary Voltage0.468 kV
Winding MaterialAL
Impedance7.5%
Tap Changer/
Tapping Range/
No Load Loss3.2 kW
On Load Loss15.6 kW
Insulation levelF
AccessoriesTemperature controller, CT(5000/1)

 

1.3 Drawings

2100kVA Resin cast dry type transformer dimensions and weight detailsdry type distribution transformer drawing

02 Manufacturing

2.1 Core

The 2100 kVA dry type distribution transformer core uses grain-oriented silicon steel sheets with high magnetic permeability, improving electromagnetic efficiency and reducing core losses. These sheets have strong mechanical properties to endure processing and long-term stress. SCOTECH ensures burrs ≤ 0.02mm and no defects. The stacked core is coated with moisture-proof epoxy resin for added durability and humidity protection.

dry type distribution transformer core

2.2 Winding

dry type distribution transformer winding with class F insulation material

The dry type distribution transformer features two windings, both constructed with durable aluminum conductors to ensure excellent performance and long service life. All windings are insulated with Class F insulation materials, and the entire coil is vacuum impregnated with Class F epoxy resin, forming a solid, moisture-resistant and thermally stable insulating system.

2.3 Final Assembly

The fabricated core and winding components are assembled, during which electrical connections, insulation, and structural fixation are performed.

Under vacuum, epoxy resin is poured between the windings and the core, forming a solid, cured structure.

After assembly and curing, a series of electrical and mechanical tests are performed to ensure the transformer meets design and safety standards.

dry type distribution transformer fabricated core and winding components are assembled

03 Testing

Routine Test

  1. Measurement of winding resistance
  2. Measurement of voltage ratio and check of phase displacement
  3. Measurement of short-circuit impedance and load loss
  4. Measurement of no-load loss and current
  5. Applied voltage test
  6. Induced voltage withstand test
  7. Partial discharge test
  8. Oil dielectric test

Test Results

 

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Measurement of winding resistance/Maximum resistance unbalance rate

Line resistance:≤2%

HV (line)LV (line)Pass
0.18%1.61%
2Measurement of voltage ratio and check of phase displacement/The tolerance of voltage ratio on the principal tapping: ±1/10

Connection symbol: D(+15°)d0

-0.18% ~ -0.07%

D(+15°)d0

Pass
3Measurement of Short-circuit Impedance and Load Loss/

kW

kW

t:120℃

Z%: measured value

Pk: measured value

Pt: measured value

8.13%

12.662

16.261

Pass
4Measurement of No-load Loss and Current at 90% and 110% of rated voltage/

kW

I0 :: provide measured value

P0: provide measured value

90% Ur110% UrPass
0.162%0.198%
2.32652.8435
5Applied Voltage Test/HV: 38kV 60s

LV: 3kV 60s

No collapse of the test voltage occursPass
6Induced Voltage Withstand Test/Applied voltage (KV):

2 Ur

Induced voltage (KV): 0.936

Duration(s):40

Frequency (HZ): 150

No collapse of the test voltage occursPass
7Partial Discharge TestpCThe maximum level of partial discharges shall be 10 pC<10Pass

 

04 Packing and Shipping

05 Site And Summary

dry type distribution transformer manufacturerThis 2100 kVA dry type distribution transformer is specially designed for a South African customer. This transformer is especially suitable for heavy-duty machinery, large motors, and processing equipment in mining and industrial applications requiring high load capacity. SCOTECH is ready to provide professional customization and quality service to meet your demands.

As a professional dry type transformer manufacturer, SCOTECH offers products compliant with international standards such as IEC, ANSI/IEEE, NEMA, CSA, and BS. Our resin cast dry type transformers cover rated powers from 50 kVA up to 15 MVA, with high voltages up to 36 kV. Both 50 Hz and 60 Hz frequencies are available, with delta or star connections. Medium voltage windings are encapsulated in epoxy resin, with insulation classes ranging from A, E, B, F to H, and protection levels customizable from IP 2X to IP 4X.

Cooling options include natural air cooling (ONAN) and forced air cooling (ONAF), equipped with multiple temperature sensors and thermal relays for reliable thermal protection. We also provide accessories such as wheels, current transformers, on-load tap changers (OLTC), and marshalling boxes to meet diverse customer needs.