  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard front view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right front 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right side view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right rear 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard rear view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard left rear 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard left front 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard front view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right front 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right side view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard right rear 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard rear view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard left rear 45deg view
  • 12 kva 11 kv to 0.22 kv dry distribution transformer iec standard left front 45deg view

12 kVA Dry Distribution Transformer-11/0.22 kV | United Arab Emirates 2025

Delivery Country: United Arab Emirates 2025
Capacity: 12kVA
Voltage: 11000/220V
Feature: with Enclosure: IP20

12 kva dry distribution transformer-main-view

Reliable power in compact form - your trusted dry distribution transformer

01 General

1.1 Project Description

This 12 kVA Cast Resin Dry-Type Transformer (CRT) is a compact and reliable solution for low-capacity three-phase power distribution. Designed according to IEC standards, it features a grain-oriented silicon steel core and copper windings, with natural air cooling (AN), a primary voltage of 11 kV and a secondary voltage of 0.22 kV.

Equipped with a Dy11 vector group and a No-Load Tap Changer (NLTC) with ±2×2.5% adjustment, this 12 kva dry distribution transformer features low no-load and load losses of 0.09 kW and 0.39 kW. Class B insulation ensures reliable and safe operation under normal conditions.

A Cast Resin Transformer (CRT), also called an Epoxy Cast Resin Dry-Type Transformer, is a dry-type transformer. The windings are fully covered with epoxy resin. It does not use oil or other liquids for insulation. Air is used to cool and insulate the core and windings.

The epoxy resin gives strong insulation and stops the transformer from absorbing moisture. This lets it work well in humid, dusty, or harsh environments. The resin is poured under vacuum. This makes sure the coils are completely sealed and protected. This dry transformer has a 12 kVA capacity and an 11 kV/0.22 kV voltage rating. It provides a stable solution for medium-to-low voltage distribution.

1.2 Technical Specification

12 kVA Resin cast dry type transformer specification and data sheet

Delivered toUnited Arab Emirates
Year2025
TypeResin cast dry type transformer
Core materialGrain oriented silicon steel sheet
StandardIEC
Rated Power12 kVA
Frequency50HZ
PhaseThree
Vector groupDy11
Cooling TypeAN
Primary Voltage11KV
Secondary Voltage0.22 kV
Winding MaterialCopper
Impedance4%
Tap ChangerNLTC
Tapping Range±2*2.5%@primary voltage
No Load Loss0.09 kW
On Load Loss0.39kW
Insulation levelB
AccessoriesTemperature controller, Enclosure

1.3 Drawings

12kVA Resin cast dry type transformer dimensions and weight details

02 Manufacturing

2.1 Core

The silicon steel has about 3% silicon. It has good magnetic performance and low loss. This helps reduce eddy currents and works well at higher frequencies. Laminated sheets of premium silicon steel minimize eddy current losses and magnetic hysteresis, enhancing energy efficiency.

2.2 Winding

12kVA Resin cast dry type transformer winding

This 12 kVA dry distribution transformer utilizes high-performance copper conductors for high strength and short-circuit resistance. The low-voltage winding utilizes a foil design to ensure uniform current distribution. The transformer utilizes Class B (130°C) insulation and epoxy resin casting technology for excellent moisture and dust resistance, while also providing reliable short-circuit protection.

2.3 IP20 Enclosure

This indoor dry-type transformer features an IP20-rated protective enclosure, effectively preventing direct contact between fingers and solid foreign objects and live components, ensuring operator safety. The enclosure also prevents dust, metal shavings, and other debris from entering the transformer, reducing the risk of insulation breakdown and localized overheating. Furthermore, the enclosure reduces operating noise and optimizes the indoor environment.

12kVA dry type transformer IP20 enclosure

2.4 Final Assembly

dry distribution transformer assembly

The fabricated core and winding components are assembled, during which electrical connections, insulation, and structural fixation are performed.
Under vacuum, epoxy resin is poured between the windings and the core, forming a solid, cured structure.
After assembly and curing, a series of electrical and mechanical tests is performed to ensure the 12 kva dry distribution transformer meets design and safety standards.

03 Testing

Testing Standard and Routine Test

IEC 60076-1-2011 Power Transformers – Part 1: General
IEC 60076-3-2013 Power Transformers – Part 3: Insulation levels, dielectric tests and external clearances in air
IEC 60076-11-2018 RLV Power Transformers – Part 11: Dry type transformer

  1. Measurement of winding resistance
  2. Measurement of voltage ratio and check of phase displacement
  3. Measurement of short-circuit impedance and load loss
  4. Measurement of no load loss and current
  5. Applied voltage test
  6. Induced voltage withstand test
  7. Partial discharge test

 

Test Results

No.Test Item

 

UnitAcceptance

Values

Measured ValuesConclusion
1Measurement of winding resistance/Maximum resistance unbalance rate

Line resistance:≤2%

HV (line)LV (line)Pass

 

0.68%0.53%
2Measurement of voltage ratio and check of phase displacement/The tolerance of voltage ratio on the principal tapping: ±1/10

Connection symbol: Dy11

0.01% ~ 0.12%

Dy11

Pass

 

3Measurement of Short-circuit Impedance and Load Loss/

kW

kW

t:100℃

Z%: measured value

Pk: measured value

Pt: measured value

3.64%

0.259

0.317

Pass

 

4Measurement of No-load Loss and Current at 90% and 110% of rated voltage/

kW

I0 :: provide measured value

P0: provide measured value

 

90% Ur2.88

0.083

Pass

 

100% Ur3.21

0.093

110% Ur3.53

0.102

5Applied Voltage Test/HV: 28kV 60s

LV 3kV 60s

No collapse of the test voltage occursPass

 

6Induced Voltage Withstand Test/Applied voltage (KV):

2 Ur

Induced voltage (KV): 0.44

Duration(s):40

Frequency (HZ): 150

No collapse of the test voltage occursPass

 

7Partial Discharge TestpCThe maximum level of partial discharges shall be 10 pC<10Pass

 

 

04 Packing and Shipping

05 Site And Summary

12kVA Resin cast dry type transformer with enclosure

In industrial and commercial buildings, a stable power supply is very important. The Scotech 12 kva dry distribution transformer gives safe and efficient medium- to low-voltage power.

It has a copper winding and a silicon steel core. The windings are fully covered in epoxy resin and air-cooled, so no oil is needed. The resin protects against moisture and dust, allowing long-term use in harsh environments.

It has a Dy11 vector group and a No-Load Tap Changer (NLTC) for flexible voltage adjustment. Low no-load and load losses make it efficient. The IP20 enclosure keeps people safe and stops dust from entering, while also reducing noise indoors.