x
Send Your Inquiry Today
Quick Quote
  • 650 kva 11 kv to 0.34 kv cast coil transformers front view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right front 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right side view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right rear 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers rear view
  • 650 kva 11 kv to 0.34 kv cast coil transformers left rear 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers left side view
  • 650 kva 11 kv to 0.34 kv cast coil transformers internal view with enclosure open
  • 650 kva 11 kv to 0.34 kv cast coil transformers with enclosure
  • 650 kva 11 kv to 0.34 kv cast coil transformers front view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right front 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right side view
  • 650 kva 11 kv to 0.34 kv cast coil transformers right rear 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers rear view
  • 650 kva 11 kv to 0.34 kv cast coil transformers left rear 45deg view
  • 650 kva 11 kv to 0.34 kv cast coil transformers left side view
  • 650 kva 11 kv to 0.34 kv cast coil transformers internal view with enclosure open
  • 650 kva 11 kv to 0.34 kv cast coil transformers with enclosure

650 KVA Cast Coil Transformers-11/0.34 KV | United Arab Emirates 2025

Delivery Country: United Arab Emirates 2025
Capacity: 650kVA
Voltage: 11000/340V
Feature: with Enclosure IP20

650 kva 11 kv to 0.34 kv cast coil transformers

Stable energy for every application - choose scotech cast coil transformers

01 General

1.1 Project Description

Our 650 kVA Cast Resin Dry-Type Transformer (CRT) provides stable power for medium-voltage to low-voltage distribution. Follow IEC standards. Featuring an input voltage of 11kV and an output voltage of 0.34 kV, with a power rating of 650 kVA. Featuring a grain-oriented silicon steel core and copper windings, the transformer operates safely while ensuring long service life. The Yd11 vector group gives a stable neutral point and balanced three-phase output, supporting a consistent voltage supply.

The 650 kVA cast coil transformers manufacturers, suppliers and factory – Scotech uses AN/AF cooling and F-class insulation, allowing it to operate safely under varying loads. Its no-load loss is 1.25 kW and load loss is 7.3 kW, which helps reduce energy consumption. The NLTC (No-Load Tap Changer) with ±2×2.5% adjustment keeps the output voltage steady.

1.2 Technical Specification

650kVA Resin cast dry type transformer specification and data sheet

Delivered toUnited Arab Emirates
Year2025
TypeResin cast dry type transformer
Core materialGrain oriented silicon steel sheet
StandardIEC
Rated Power650kVA
Frequency50HZ
PhaseThree
Vector groupYd11
Cooling TypeAN/AF
Primary Voltage11KV
Secondary Voltage0.34 kV
Winding MaterialCopper
Impedance6%
Tap ChangerNLTC
Tapping Range±2*2.5%@primary voltage
No Load Loss1.25 kW
On Load Loss7.3 kW
Insulation levelF
AccessoriesTemperature controller, Cooling fans, Enclosure

1.3 Drawings

650kVA Resin cast dry type transformer drawing and weight details

02 Manufacturing

2.1 Core

The core of our dry-type transformer is made with grain-oriented silicon steel sheets. It uses a step-lap joint design with 45° mitred, hole-free laminations. This design lowers no-load losses and also reduces noise. The transformer runs in a stable and quiet way.

2.2 Winding

650 kva cast coil transformer winding

The 650 kVA cast coil transformers coils are made of high-conductivity copper, providing high mechanical strength and short-circuit resistance. The windings utilize Class F (155°C) insulation and are epoxy-casted for reliable protection against moisture, dust, and short circuits, ensuring long-term safe and stable operation.

2.3 IP20 Enclosure

Our indoor dry-type transformers feature an IP20-rated protective enclosure, providing comprehensive protection: preventing accidental contact with high-voltage components, isolating dust and foreign objects, and extending the transformer’s service life. The enclosed enclosure also reduces operating noise and enhances indoor working comfort. Its aesthetically pleasing design and compact structure provide customers with a safe, reliable, and easy-to-maintain power distribution solution.

650 kva cast coil transformer  IP20 enclosure

2.4 Final Assembly

650 kva cast coil transformers-back-viewDuring assembly, each dry-type transformer is equipped with a temperature controller and PT100 temperature probes built into the three-phase windings. These monitor winding temperatures in real time and display them on a digital display. Six high-efficiency cooling fans optimize heat dissipation and ensure long-term stable operation. Each product undergoes multiple rigorous inspections and tests during the manufacturing process and is thoroughly inspected again before shipment. We are committed to providing customers with a reliable, safe, and high-performance dry-type transformer experience.

03 Testing

Testing Standard and Routine Test

IEC 60076-1-2011 Power Transformers – Part 1: General
IEC 60076-3-2013 Power Transformers – Part 3: Insulation levels, dielectric tests and external clearances in air
IEC 60076-11-2018 RLV Power Transformers – Part 11: Dry type transformer

  1. Measurement of winding resistance
  2. Measurement of voltage ratio and check of phase displacement
  3. Measurement of short-circuit impedance and load loss
  4. Measurement of no load loss and current
  5. Applied voltage test
  6. Induced voltage withstand test
  7. Partial discharge test

Test Results

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Measurement of winding resistance

 

/Maximum resistance unbalance rate

Line resistance:≤2%

HV (line)LV (line)Pass

 

0.19%0.84%
2Measurement of voltage ratio and check of phase displacement/The tolerance of voltage ratio on the principal tapping: ±1/10

Connection symbol: Yd11

0.02% ~ 0.17%

Yd11

Pass

 

3Measurement of Short-circuit Impedance and Load Loss/

kW

kW

t:120℃

Z%: measured value

Pk: measured value

Pt: measured value

6.09%

5.857

7.338

Pass

 

4Measurement of No-load Loss and Current at 90% and 110% of rated voltage/

kW

I0 :: provide measured value

P0: provide measured value

90% Ur0.44

1.000

Pass

 

100% Ur0.49

1.112

110% Ur0.53

1.223

5Applied Voltage Test/HV: 35kV 60s

LV: 3kV 60s

No collapse of the test voltage occursPass

 

6Induced Voltage Withstand Test/Applied voltage (KV):

2 Ur

Induced voltage (KV): 0.68

Duration(s):40

Frequency (HZ): 150

No collapse of the test voltage occursPass

 

7Partial Discharge TestpCThe maximum level of partial discharges shall be 10 pC<10Pass

 

04 Packing and Shipping

05 Site And Summary

The Scotech 650 kVA Cast Resin Dry-Type Transformer delivers safe and stable power for industrial and commercial applications. It has a silicon steel core and copper windings fully covered in epoxy resin, allowing long-term operation without oil.

The 650 kVA cast coil transformer has a Yd11 vector group and a No-Load Tap Changer (NLTC) to keep voltage steady under changing loads. AN/AF cooling and Class F insulation allow it to run safely at high temperatures. Low no-load and load losses help reduce energy use.

The IP20 enclosure keeps people safe and stops dust and objects from entering. Built-in temperature sensors and cooling fans help the transformer run reliably.