x
Send Your Inquiry Today
Quick Quote
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding front view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding right front 45deg view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding right side view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding top view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding left side view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding left rear 45deg view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding rear view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding front view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding right front 45deg view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding right side view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding top view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding left side view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding left rear 45deg view
  • 75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding rear view

75 kVA Transformer Power Lines-13.8/0.12*0.24 kV | Guyana 2024

Delivery Country: Guyana 2024
Capacity: 75kVA
Voltage: 13.8/0.12*0.24 kVA
Feature: with IFD

75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding main view

Trusted 75kVA Pole-Mount Transformers - SCOTECH Powering Communities Since 1999

01 General

1.1 Project Description

This 75kVA single-phase pole-mounted transformer was delivered to Guyana in 2024. Rigorously comply with IEEE & ANSI C57.12.00 standards. The polarity is subtractive, and the vector group is Ii0. Rated for a primary voltage of 13,800V and a secondary voltage of 120/240V, making it suitable for residential and small commercial applications.

The power lines transformer features copper windings for enhanced conductivity and efficiency. An impedance of 2%, ensuring minimal voltage drop under load. ±2.5% tapping range, with a total range of 10%. Offers customizable voltage regulation settings, allowing fine‑tuned control to meet specialized power needs.

SCOTECH has over 25 years of experience in transformer manufacturing. Even large orders can be delivered on time with the team’s cooperation.

1.2 Technical Specification

75kVA Single phase pole mounted transformer specification and data sheet

Delivered toGuyana
Year2024
TypeSingle phase pole mounted transformer
StandardIEEE & ANSI C57.12.00
Rated Power75KVA
Frequency60HZ
PolaritySubtractive
Vector groupIi0
Primary Voltage13800V
Secondary Voltage120/240V
Winding MaterialCOPPER
Impedance2%
Cooling MethodONAN
Tap ChangerNLTC
Tapping Range±2X2.5%(Total range=10%)
No Load Loss214W
On Load Loss713W
AccessoriesStandard Configuration

1.3 Drawings

75kVA Single phase pole mounted transformer dimensions and weight details

02 Manufacturing

2.1 Core

Wound cores are compact and lightweight, making them ideal for single-phase pole-mounted transformers. Wound cores have fewer joints, and their magnetic flux path aligns with the rolling direction of the magnetic steel sheets, resulting in lower continuous no-load losses. Another advantage of wound cores is that they are quieter than laminated cores.75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer with copper winding iron core

2.2 Winding

Our transformer windings use high-purity enameled round copper wire, featuring excellent electrical conductivity and compact insulation.  Round copper wire is easy to handle and suitable for high-speed automated winding. Adopt an optimized coil structure of foil winding for low-voltage coils and wire winding for high-voltage coils, ensuring excellent operational stability, reliability, and thermal performance.

2.3 Tank

Inside and outside the tank, all welding slag and spatter must be fully removed, with special attention to radiator bases and lifting lugs to avoid dead spots. After sandblasting, the first anti-rust primer must be applied within six hours; beyond that, re-sandblasting is required. Coatings must be applied in two primer coats and two topcoats, with a total thickness of 80 mil, strong adhesion, and a smooth, even, glossy finish.

2.4 Final Assembly

75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer copper winding and iron core1. Winding Assembly: Slide the HV/LV windings onto the laminated core, ensuring proper alignment and insulation integrity.
2. Electrical Connections: Connect winding leads to tap changer, bushings, and other components, then secure and insulate the joints.
3. Core-Coil Drying: Place the assembled active part (core + windings) into a drying oven for vacuum heating to remove moisture.
4. Tank Installation: Hoist the dried active part into the tank, position it securely, and ensure proper insulation from the tank walls.
5. Accessory Mounting: Install bushings, pressure relief valve and other accessories, then check for leaks.
6. Oil Filling & Settling: Vacuum-fill with insulating oil, degas, and allow settling before checking oil levels and dielectric strength.

03 Testing

Routine Test

  1. Resistance Measurements
  2. Ratio Tests
  3. Polarity Test
  4. No Load Losses and No Load Current
  5. Load Losses and Impedance Voltage
  6. Applied Voltage Test
  7. Induced Voltage Withstand Test
  8. Insulation Resistance Measurement
  9. Leak Testing with Pressure for Liquid Immersed Transformers
  10. Oil Dielectric Test

75 kva 13.8 kv to 0.12kv 0.24kv dual secondary pole mounted transformer routine examination

Test Results

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Resistance Measurements///Pass

 

2Ratio Tests/The deviation of voltage ratio on the principal tapping: ≤0.5%

Connection symbol: Ii0

-0.02Pass

 

3Polarity tests/SubtractiveSubtractivePass

 

4No-load losses and excitation current%

kW

I0 :: provide measured value

P0: provide measured value

the tolerance for no load loss is +10%

0.49

0.174

Pass

 

5Load losses , impedance voltage,total losses and efficiency/

kW

kW

t:85℃

Z%: measured value

Pk: measured value

Pt: measured value

the tolerance for impedance is ±10%

the tolerance for total load loss is +6%

1.98

0.710

0.884

99.11

Pass

 

6Applied Voltage Test/HV:34KV 60s

LV: 10kV 60s

No collapse of the test voltage occursPass

 

7Induced Voltage Withstand Test/Applied voltage (KV):

2 Ur

Duration(s): 48

Frequency (HZ): 150

No collapse of the test voltage occursPass

 

8Insulation Resistance MeasurementGΩHV-LV to Ground

LV-HV to Ground

HV&LV to Ground

77.3

68.9

64.5

/
9Leakage Test/Applied pressure:20kPA

Duration:12h

No leakage and no

Damage

Pass

 

10Oil Dielectric TestkV≥4552.00Pass

 

04 Packing and Shipping

05 Site and Summary

Reliable and efficient, this 75 kVA transformer power lines was built for Guyana. With high-quality copper windings, durable tank design, and strict quality control, it ensures stable power distribution and long-term performance.