  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer front view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer right front 45deg view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer right side view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer rear view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer left side view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer front view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer right front 45deg view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer right side view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer rear view
  • 50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer left side view

50 kVA Transformer On Power Pole-7.97/0.12/0.24 kV | Canada 2024

Delivery Country: Canada 2024
Capacity: 50kVA
Voltage: 7.97/0.12/0.24 kV
Feature: Amorphous core

50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer

A reliable transformer on power pole delivering efficient and stable energy for modern communities

01 General

1.1 Project Description

This 50 kVA single-phase pole-mounted distribution transformer strictly adhere to IEEE C57.12.20 standards. It is widely used in North American distribution networks, typically installed in 13.8 kV grounded-wye systems, where the transformer is connected phase-to-neutral at 7.97 kV and provides a reliable 120/240 V split-phase output for residential and light commercial applications.

The 50 kVA transformer on power pole adopts an amorphous metal core, which greatly reduces no-load loss to only 0.043 kW. It gives very good energy-saving performance even at light load. With a rated impedance of 2.1%, the transformer offers good voltage regulation and, together with its ±2×2.5% no-load tap changer, ensures stable secondary voltage within ±5% of nominal.

Its design features include ONAN natural cooling, aluminum windings, and additive polarity, with vector group Ii6. These features make the transformer compact. It is efficient and reliable for pole-mounted use. The unit has a surge arrester boss. This makes it easy to add protective devices.

The transformer has low losses. It works with high efficiency. It also adapts well to different needs. This makes it a good choice for modern power distribution systems.

 

1.2 Technical Specification

50kVA Single phase pole mounted transformer specification and data sheet

Delivered toCanada
Year2024
TypeSingle phase pole mounted transformer
StandardIEEE C57.12.20
Rated Power50KVA
Frequency60HZ
PolarityAdditive
Vector groupIi6
Primary Voltage7.97/13.8Y kV
Secondary Voltage120/240V
Winding MaterialAluminum
Impedance2.1%
Cooling MethodONAN
Tap ChangerNLTC
Tapping Range±2X2.5%
No Load Loss0.043 KW
On Load Loss0.5 KW
AccessoriesSurge arrester boss

1.3 Drawings

50kVA transformer on power pole drawing and nameplate

02 Manufacturing

2.1 Core

The pole-mounted transformer features an amorphous metal core, made from a melt of iron, boron, silicon, nickel, and carbon. Compared to conventional cold-rolled silicon steel, this core is isotropic, extremely thin (0.03 mm), and has high electrical resistivity, significantly reducing eddy current losses. It achieves remarkably low no-load loss (0.043 kW) and load loss (0.5 kW), offering high efficiency, simplified manufacturing, and eco-friendly operation.50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer iron cores

2.2 Winding

50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer windingsOur single-phase pole-mounted transformers feature low-voltage foil coils and high-voltage wire coils. Customers choosing aluminum LV coils benefit from reduced weight and cost, while maintaining comparable reliability and operating life to copper. High-voltage wire coils ensure insulation and voltage balance.

2.3 Tank

This single-phase cylindrical fuel tank is constructed from mild steel, with the cover and bottom formed using a thin-sheet drawing process.  Equipped with two HV bushings on the cover and three LV eyebolt bushings on the sidewall, its fully sealed design ensures superior leak resistance and operational reliability.50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer oil tanks

2.4 Final Assembly

50 kva 7.97 kv to 0.12kv 0.24kv dual secondary pole mounted transformer active partsHow to install the coil and wound core: First, lay the first C-core flat (opening facing up like a “U”). Take the coil and fully sleeve its central hole onto one leg of the core, pushing it down to the bottom. Take the second C-core, align its cut precisely with the first core’s cut. Gently close it until the two parts fully mate. Install the top and bottom clamping plates, insert the long screws.

03 Testing

Routine Test

  1. Resistance Measurements
  2. Ratio Tests
  3. Polarity Test
  4. No Load Losses and No Load Current
  5. Load Losses and Impedance Voltage
  6. Applied Voltage Test
  7. Induced Voltage Withstand Test
  8. Insulation Resistance Measurement
  9. Leak Testing with Pressure for Liquid Immersed Transformers
  10. Oil Dielectric Test

Test Results

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Resistance Measurements%//Pass

 

2Ratio Tests%The deviation of voltage ratio on the principal tapping: ≤0.5%

Connection symbol: Ii6

0.02Pass

 

3phase-relation tests/AdditiveAdditive 

Pass

 

4No-load losses and excitation current

 

%

kW

t:85℃

I0 :: provide measured value

P0: provide measured value

the tolerance for no load loss is +10%

1.11(100%)

2.16(105%)

0.045(100%)

0.061(105%)

Pass

 

5Load losses impedance voltage and efficiency

 

%

kW

kW

t:85℃

Z%: measured value

Pk: measured value

Pt: measured value

the tolerance for impedance is ±10%

the tolerance for total load loss is +6%

2.21

0.496

0.543

99.37

Pass

 

6Applied Voltage TestkVHV: 34kV 60s

LV:10kV 60s

No collapse of the test voltage occursPass

 

7Induced Voltage Withstand TestkVApplied voltage (KV):

15.94

Duration(s):40

Frequency (HZ): 150

No collapse of the test voltage occursPass

 

8Leakage TestkPaApplied pressure:20kPA

Duration:12h

No leakage and no

Damage

Pass

 

9Insulation Resistance MeasurementGΩHV&LV to Ground:120.0/
HV-LV to Ground51.8
LV-HV to Ground62.6
10Oil Dielectric TestkV≥4555.48Pass

 

11Lightning impulse testkVfull wave, Half waveNo collapse of the test voltage occursPass

 

04 Packing and Shipping

05 Site and Summary

This 50 kVA single-phase pole-mounted transformer is made for Canada in 2024. It follows IEEE C57.12.20. It works on 13.8 kV grounded-wye systems, giving 120/240 V for houses and small businesses.

The transformer has an amorphous metal core. It keeps no-load loss at 0.043 kW and load loss at 0.5 kW. It saves energy and runs with high efficiency. Aluminum windings, ONAN cooling, and additive polarity make the unit compact, safe, and reliable. The surge arrester boss allows easy protection upgrades.

This transformer on power pole combines efficiency, reliability, and eco-friendly performance, making it a strong choice for modern distribution networks.

Scotech makes quality transformers for global customers. Our products save energy, cut losses, and give stable power. We deliver safe and proven solutions that help power grids work better every day.

Scotech – reliable transformers, efficient power, better networks.