x
Send Your Inquiry Today
Quick Quote
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer front view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer right front 45deg view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer right side view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer left rear 45deg view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer left side view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer front view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer right front 45deg view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer right side view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer left rear 45deg view
  • 75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer left side view

75 kVA Pole Mounted Transformer-7.97/0.12*0.24 kV | Canada 2024

Delivery Country: Canada 2024
Capacity: 75kVA
Voltage: 7.97/0.12*0.24 kV
Feature: with no-load tap changer

75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer

Efficient, reliable, and eco-friendly—powering your distribution network with Scotech’s 50 kVA pole-mounted transformer

01 General

1.1 Project Description

These 75 kVA single-phase pole mounted transformers manufactured by Scotech. Pole-mounted transformers step down high-voltage electricity to levels suitable for households and small businesses, ensuring a stable power supply in urban and rural areas. These transformers are exported to Canada, fully complying with IEEE C57.12.20 standards and meeting modern utility requirements for energy efficiency.

The order includes 8 units of the 75 kVA transformer. Each unit is designed for a high voltage of 7.97/13.8Y kV and a low voltage of 120/240 V split-phase. Equipped with two high voltage bushings and three low voltage bushings, the transformer ensures reliable service for residential and light commercial applications.

The transformer provides four tapping positions on the high voltage side with a range of ±2 × 2.5%, giving utilities flexibility to adjust voltage according to line conditions.

With a rated impedance of 2.1%, a no-load loss of 0.148 kW, and a load loss of 0.675 kW, it demonstrates high efficiency and low operating losses. It adopts ONAN cooling, aluminum windings, and additive polarity, designed for compact size and easy pole-mounted installation.

The transformer is also equipped with a surge arrester boss, allowing integration of protective devices for improved safety and reliability in distribution networks.

1.2 Technical Specification

75kVA pole mounted transformer specification and data sheet

Delivered toCanada
Year2024
TypeSingle phase pole mounted transformer
StandardIEEE C57.12.20
Rated Power75 kVA
Frequency60HZ
PolarityAdditive
Vector groupIi6
Primary Voltage7.97/13.8Y kV
Secondary Voltage120/240V
Winding MaterialAluminum
Impedance2.1%
Cooling MethodONAN
Tap ChangerNLTC
Tapping Range±2X2.5%
No Load Loss0.148 KW
On Load Loss0.675 KW
AccessoriesSurge arrester boss

1.3 Drawings

75kVA pole mounted transformer dimensions and weight details

02 Manufacturing

2.1 Core

75 kVA single-phase pole-mounted transformers utilize high-quality silicon steel laminations. Silicon steel is the most common material for transformer cores. It possesses magnetic properties, including high permeability and low core losses. Compared to traditional laminated cores, wound cores are lightweight, enabling the construction of more compact and lightweight transformers.75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer electrical steel core

2.2 Winding

75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer winding The transformer’s windings are expertly handcrafted by veteran workers with over a decade of experience. The low-voltage winding is foil-wound, and the high-voltage winding is wire-wound, with precise control of tension to prevent foil lifting. Inter-turn and inter-layer insulation are carefully applied to avoid partial discharge.

2.3 Tank

The cylindrical fuel tank is made of mild steel. Thin-sheet stretching technology makes the lid and bottom lightweight and strong. The tank is fully sealed. This design makes it more adaptable to the environment and more reliable in use. It works well for outdoor uninterrupted power supply.75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer tank enclosure

2.4 Final Assembly

75 kva 7.97 kv to 0.12kv 0.24kv dual secondary 75 kva pole mounted transformer final assembly How to install the coil and wound core: First, lay the first C-core flat (opening facing up like a “U”). Take the coil and fully sleeve its central hole onto one leg of the core, pushing it down to the bottom. Take the second C-core, align its cut precisely with the first core’s cut. Gently close it until the two parts fully mate. Install the top and bottom clamping plates, insert the long screws.

03 Testing

  1. Routine Test
    1. Resistance Measurements
    2. Ratio Tests
    3. Phase-relation Test
    4. No Load Losses and No Load Current
    5. Load Losses, Impedance Voltage and Efficiency
    6. Applied Voltage Test
    7. Induced Voltage Withstand Test
    8. Leak Testing with Pressure for Liquid Immersed Transformers
    9. Insulation Resistance Measurement
    10. Oil Dielectric Test
    11. Lightning Impulse Test

Test Results

No.Test Item

 

Unit

 

Acceptance

Values

Measured ValuesConclusion
1Resistance Measurements%//Pass

 

2Ratio Tests%The deviation of voltage ratio on the principal tapping: ≤0.5%

Connection symbol: Ii6

-0.03Pass

 

3phase-relation tests/AdditiveAdditivePass

 

4No-load losses and excitation current%

kW

t:85℃

I0 :: provide measured value

P0: provide measured value

the tolerance for no load loss is +10%

0.24(100%)

0.46(105%)

0.144(100%)

0.167(105%)

Pass

 

5Load losses impedance voltage and efficiency

 

%

kW

kW

t:85℃

Z%: measured value

Pk: measured value

Pt: measured value

the tolerance for impedance is ±10%

the tolerance for total load loss is +6%

2.19

0.688

0.838

99.19

Pass

 

6Applied Voltage TestkVHV: 34kV 60s

LV:10kV 60s

No collapse of the test voltage occurs

 

Pass

 

7Induced Voltage Withstand TestkVApplied voltage (KV):

15.94

Duration(s):40

Frequency (HZ): 150

No collapse of the test voltage occurs

 

Pass

 

8Leakage TestkPaApplied pressure:20kPA

Duration:12h

 

No leakage and no

Damage

 

Pass

 

9Insulation Resistance Measurement

 

GΩHV&LV to Ground:97.1/
HV-LV to Ground36.1
LV-HV to Ground45.5
10Oil Dielectric TestkV≥4555.50Pass

 

11Lightning impulse testkVfull wave, Half waveNo collapse of the test voltage occursPass

 

04 Packing and Shipping

05 Site and Summary

The 75 kVA single-phase pole mounted transformer is made for Canada in 2024. It follows IEEE C57.12.20. It works on 13.8 kV grounded-wye systems and gives 120/240 V split-phase output for houses and small businesses.

The transformer has a high-quality silicon steel core. It keeps no-load loss at 0.148 kW and load loss at 0.675 kW. It runs with high efficiency and low operating cost. The windings are aluminum, with foil-wound LV coils and wire-wound HV coils. The winding work is done by skilled workers, ensuring strong insulation and safe operation.

The tank is made of mild steel. It is fully sealed, light, and strong. It gives good protection outdoors and works well in long-term service. The unit also has a surge arrester boss, which makes it easy to add protection.