Energy on the pole, power at heart – Single-phase pole-mounted transformer, making electricity outstanding.
01 General
1.1 Project Description
SCOTECH is glad to provide a high-quality single-phase pole mounted transformer for the Canadian Public Service. The single-phase transformer has a capacity of 100kVA, the primary voltage is 7.97/13.8Y and the secondary voltage is 0.12/0.24kV, which can easily meet local electricity demand. The single phase pole mounted transformer converts the voltage of the grid into the voltage required by the system or load, and realizes the transmission and distribution of electric energy. The large-scale operation of this product can achieve a good energy saving effect and reduce air pollution. This product is especially suitable for power shortage and load fluctuation and difficult to carry out daily maintenance in areas. Because the transformer adopts a fully sealed structure, insulating oil and insulating media are not polluted by the atmosphere, so it can operate in a humid environment, and is the ideal distribution equipment in the vast distribution network in cities and rural areas. Single-phase transformers are especially suitable for rural power grids, remote mountainous areas, scattered villages, agricultural production, lighting and power consumption. can also be used for railway, urban power grid energy-saving transformation column type distribution lines, can be single-phase operation or three single-phase groups as three-phase operation.
Our 100 kVA pole mounted transformer was designed with advanced technology and adopts high quality material and components which result in reliable quality and long operation time.
1.2 Technical Specification
100 kVA transformer specifications type and data sheet
| Delivered to | Canada |
| Year | 2024 |
| Type | Pole mounted transformer |
| Standard | IEEE C57.12.20 |
| Rated Power | 100KVA |
| Winding | Aluminum |
| Polarity | Additive |
| Frequency | 60HZ |
| Phase | 1 |
| Cooling Type | ONAN |
| Primary Voltage | 7.97/13.8Y KV |
| Dual Primary Voltage | No |
| Secondary Voltage | 0.24/0.12 KV |
| Vector Group | Ii0 |
| Impedance | 2.2% |
| Tap Changer | NLTC |
| Liquid Insulant | Mineral Oil |
| Tapping Range | ±2*2.5% |
| No Load Loss | 0.068KW |
| On Load Loss | 0.98KW |
| Tolerance | 10%NLL,6%Total Loss |
| Accessories | Standard Configuration |
1.3 Drawings
100 kVA pole mounted transformer diagram drawing and size.
02 Manufacturing
2.1 Core
| The advantages of transformer coil core are mainly reflected in its excellent electromagnetic performance and efficient energy transmission capacity. The efficiency of the transformer is improved because the winding process reduces the air gap and loss. This design helps reduce noise and vibration and improves overall performance. Coil core can effectively reduce eddy current loss due to its uniform flux distribution. In addition, the rolling process provides a tighter structure, improves mechanical strength and durability, and ADAPTS to high temperature and humid environments. The coil core also reduces noise and vibration in operation, making the equipment more stable, able to adapt to various working environments, and extending the service life of the equipment. | ![]() |
2.2 Winding
As a part of the winding, the low-voltage foil winding can effectively shield the electromagnetic field of the high-voltage winding, thus reducing the influence of electromagnetic interference (EMI). When the transformer shares space with other electronic devices, it can reduce interference between electronic devices and improve the electromagnetic compatibility of the overall system. As a part of the winding, the low-voltage foil winding can effectively shield the electromagnetic field of the high-voltage winding, thus reducing the influence of electromagnetic interference (EMI). When the transformer shares space with other electronic devices, it can reduce interference between electronic devices and improve the electromagnetic compatibility of the overall system. Due to the structure characteristics of low-voltage foil winding, it can effectively disperse the local heat generated by short circuit fault, reduce the risk of instantaneous impact of short circuit current on the winding, and improve the safety and reliability of the transformer. The rational layout of low-voltage and high-voltage winding design can effectively reduce the phenomenon of magnetic leakage and further improve the energy efficiency and performance of the transformer. By optimizing the arrangement between the windings, better flux coupling can be achieved, thereby improving the overall efficiency of the transformer.
2.3 Tank
![]() | According to the design drawings, the equipment such as a plasma cutting machine, laser cutting machine or water knife, is used to cut the metal sheet material into various parts of the tank, including the bottom plate of the tank, the side wall of the cylinder, the top cover, etc. The cut metal plate is processed into a cylinder shape by a rolling machine to ensure that the outline is rounded and meets the design standard. The individual components of the tank are fully welded using processes such as gas shielded welding (MIG welding) or arc welding, and the welds should be uniform and smooth and have good sealing. After welding, the surface of the tank should be decontaminated to remove welding slag, oxide layer and oil. Anti-corrosion coatings are sprayed on the outside of the tank to prevent corrosion caused by environmental impacts in daily use. The inner wall can also be treated with anti-corrosion to increase the service life of the insulating oil. |
2.4 Final Assembly
03 Testing
| No. | Test Item | Unit | Acceptance Values | Measured Values | Conclusion |
| 1 | Resistance Measurements | % | / | / | Pass |
| 2 | Ratio Tests | % | The deviation of the voltage ratio on the principal tapping: ≤0.5% Connection symbol: Ii6 | -0.02 | Pass |
| 3 | phase-relation tests | / | Additive | Additive | Pass |
| 4 | No-load losses and excitation current | % kW | t: 85℃ I0: provide measured value P0: provide measured value the tolerance for no load loss is +10% | 0.39(100%) 1.00(105%) 0.056(100%) 0.067(105%) | Pass |
| 5 | Load losses impedance voltage and efficiency | % kW kW | t: 85℃ Z%: measured value Pk: measured value Pt: measured value The tolerance for impedance is ±10% the tolerance for total load loss is +6% | 2.20 0.868 0.927 99.49 | Pass 合格 |
| 6 | Applied Voltage Test | kV | HV: 34kV 60s LV: 10kV 60s | No collapse of the test voltage occurs | Pass |
| 7 | Induced Voltage Withstand Test | kV | Applied voltage (KV): 15.94 Duration(s): 40 Frequency (HZ): 150 | No collapse of the test voltage occurs | Pass |
| 8 | Leakage Test | kPa | Applied pressure: 20kPA Duration: 12h | No leakage and no Damage | Pass |
| 9 | Insulation Resistance Measurement | GΩ | HV&LV to Ground: | 90.7 | / |
| HV-LV to Ground | 16.4 | ||||
| LV-HV to Ground | 16.9 | ||||
| 10 | Oil Dielectric Test | kV | ≥45 | 55.38 | Pass |
| 11 | Lightning impulse test | kV | full wave, Half wave | No collapse of the test voltage occurs | Pass |
04 Packing and Shipping
4.1 Packing
8.spray forklift identification, center of gravity identification | ![]() |
4.2 Shipping
![]() | 1. Loading and unloading: The hoisting equipment is used in the loading and unloading process to ensure that there is no additional mechanical stress during the transportation of the transformer. 2. Fixed: During transportation, the transformer needs to be properly fixed to prevent tilt or collision, resulting in mechanical damage. 3. Protection: Measures need to be taken to protect the insulated part of the transformer and the external structure to prevent contamination or damage. |
05 Site And Summary
Thank you for your interest in our Single-Phase Pole-Mounted Transformer! With its high efficiency, stability, and durability, this product is widely used in various power transmission and distribution scenarios, providing reliable power solutions for our customers. We always prioritize customer needs, focus on technological innovation and quality improvement, and are committed to delivering superior service and product experiences. For further information or support, please feel free to contact us!