25 kVA Transformer Pole Mounted-14.4/0.12 kV | Canada 2025

Country: Canada 2025
Capacity: 25 kVA
Voltage: 25D-0.208/0.12 kV
Feature: with surge arrester boss

25 kva transformer pole mounted

Elevate Your Grid with Our Pole Mounted Transformer Solutions.

01 General

1.1 Project Description

25 kVA single phase pole mounted transformer was delivered to Canada in 2025. The rated power of the transformer is 25 kVA with ONAN cooling. The high voltage is 25D kV with ±2*2.5% tapping range (NLTC), the low voltage is 0.208/0.12 kV, they formed a vector group of Ii6.

As a ubiquitous and trusted component of the electrical landscape, the Single-Phase Pole-Mounted Transformer stands as a silent sentinel of power distribution. Primarily serving residential areas, rural routes, and light commercial applications, its core mission is to reliably step down the higher voltages of distribution lines to the safe, usable levels required in homes and businesses. Engineered for simplicity, durability, and minimal maintenance, these units are designed to withstand the rigors of the outdoor environment-from temperature extremes to moisture and UV exposure. Their iconic pole-top placement allows for efficient use of space and straightforward integration into existing overhead networks. For utilities, this translates to a cost-effective, field-proven solution that forms the vital final link in delivering electricity, day in and day out, to the communities they serve.

1.2 Technical Specification

25 KVA pole mounted transformer specifications type and data sheet

Delivered toCanada
Year2025
TypePole mounted transformer
StandardCSA C2.2-06
Rated Power25 kVA
Frequency60HZ
Phase1
PolarityAdditive
Cooling TypeONAN
Primary Voltage25 kV
Secondary Voltage0.208/0.12 kV
Winding MaterialCopper
Angular displacementIi6
Impedance≥1.5%
Tap ChangerNLTC
Tapping Range±2*2.5%
No Load Loss0.085 kW
On Load Loss0.392 kW

1.3 Drawings

25 kVA pole mounted transformer diagram drawing and size.

02 Manufacturing

2.1 Core

The wound core of a single-phase pole-mounted transformer is formed by continuously winding high-quality silicon steel strips. It has a compact structure, low magnetic resistance and iron loss, which well adapts to the space-limited pole-mounted installation scenario.wound core of a single-phase pole-mounted transformer

2.2 Winding

Typically arranged in a concentric configuration, the windings are made of insulated conductors wound on a bobbin. The inner low-voltage winding and the outer high-voltage winding are separated by insulating barriers and cooling ducts. This compact and mechanically strong arrangement is crucial for effective energy transfer, heat dissipation, and withstanding the electrical stresses encountered in distribution networks.

2.3 Tank

smooth-walled tankManufactured through a roll-forming and circumferential welding process, this smooth-walled tank lacks corrugations or fins to maximize internal volume and structural simplicity. Its robust, welded construction prioritizes leak-proof integrity and cost-effectiveness, with cooling achieved solely through the plain surface of the cylindrical shell.

2.4 Final Assembly

The complete assembly integrates the core-coil assembly into the cylindrical tank, followed by the sealing of the cover and the mounting of all bushings. A critical vacuum drying process is then conducted to remove moisture before the tank is filled with purified insulating oil, ensuring optimal dielectric strength and long-term operational stability.integrates the core-coil assembly into the cylindrical tank

03 Testing

The test for the 25kVA-25/0.12kV single phase pole mounted transformer was conducted on 2025-04-25 per CSA C2.2-06(R2022) and CSA C802.1-13(R2022). Routine tests included winding resistance, ratio (deviation +0.05~+0.07%), polarity (additive), no-load loss/current (74.6W/0.36% at 100%), load loss/impedance (384W, 2.51%), voltage withstand, insulation resistance (41.2GΩ max), 20kPa/12h leak test, and oil test (dielectric strength 58.3kV). All passed. The report requires 7-day objection period, no unauthorized copying, and is invalid without tester/verifier/approver signatures.

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Resistance Measurements///Pass
2Ratio Tests/The deviation of voltage ratio on the principal tapping: ±0.5%

Connection symbol: Ii6

+0.05~+0.07Pass
3Polarity tests/AdditiveAdditivePass
4No-load losses and excitation current%I0 :: provide measured value(100%)0.36Pass
kWP0: provide measured value(100%)0.0746
%I0 :: provide measured value(105%)0.41
kWP0: provide measured value(105%)0.0848
/the tolerance for no load loss is +15%/
5Load losses , impedance voltage,total losses and efficiency/t:85℃

the tolerance for impedance is ≥1.5%

the tolerance for total load loss is +8%

/Pass
%Z%: measured value2.51
kWPk: measured value0.384
kWPt: measured value0.4586
%Efficiency not less than 98.63%98.72
6Applied Voltage Test/LV: 10kV 60s

HV:40kV 60s

No collapse of the test voltage occursPass
7Induced Voltage Withstand Test/Applied voltage (KV):0.24No collapse of the test voltage occursPass
Duration(s):40
Frequency (HZ): 180
8Insulation Resistance MeasurementGΩHV-LV·to·Ground41.2Pass
LV-HV to Ground39.9
HV&LV to Ground38.3
9Leakage Test/Applied pressure:20kPANo leakage and no

Damage

Pass
Duration:12h
10Oil TestkVDielectric Strength58.3Pass
mg/kgMoisture Content10.5
%Dissipation Factor0.281
mg/kgFuran Analysis≤0.1
/Gas Chromatography Analysis/

04 Packing and Shipping

4.1 Packing

sturdy wooden crateFor shipment, the transformer is enclosed in a sturdy wooden crate, constructed to its specific dimensions. The internal space is filled with blocking and bracing materials to prevent any movement, ensuring the equipment arrives undamaged and ready for installation.

4.2 Shipping

The single phase pole mounted transformer is transported under the CIF (Cost, Insurance and Freight) term to the port of EDMONTON. The seller arranges ocean freight, covers the cost of transporting the transformer (packaged in a wooden case) to EDMONTON Port, and purchases cargo insurance to protect against risks like damage or loss during transit. Risk of the transformer transfers to the buyer once the goods cross the ship’s rail at the loading port, and the buyer takes delivery at EDMONTON Port upon arrival.transported under the CIF (Cost, Insurance and Freight) term

05 Site And Summary

Designed for seamless outdoor power distribution, our single phase pole mounted transformer combines efficiency, durability, and compliance to meet your specific needs. With optimized no-load/load loss performance, additive polarity, and ±2×2.5% tapping for flexible voltage adjustment, it adapts effortlessly to diverse grid requirements. Crafted with high-quality materials and rigorously tested (including insulation, voltage withstand, and leak resistance checks), it ensures safe, consistent operation for years. To explore how this transformer elevates your power system or to request a quote, connect with us now.

25 kva transformer pole mounted manufacturer