  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators front view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators right front 45deg
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators right rear 45deg
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators rear view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators left side view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators top view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators front view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators right front 45deg
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators right rear 45deg
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators rear view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators left side view
  • 100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators top view

100 kVA transformer pole mounted-13.8/0.24*0.12 kV | Guyana 2025

Delivery Country: Guyana 2025
Capacity: 25kVA
Voltage: 13.8kV-240/120V

100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators

100 kVA single-phase pole mounted transformer-built for stable power in low-density, long-distance distribution areas

01 General

1.1 Project Description

This 100 kVA single-phase pole mounted transformer, delivered to Guyana in 2025, is designed in compliance with IEEE and ANSI C57.12.00 standards. With a primary voltage of 13,800 V and a secondary voltage of 120/240 V, it is ideal for residential or light commercial distribution in rural or suburban areas where single-phase service is required. The ONAN cooling, copper windings, and subtractive polarity ensure high reliability and durability in outdoor environments. Its ±2×2.5% NLTC tap changer allows for minor voltage regulation, making it suitable for areas with voltage fluctuation or long-distance transmission. The compact, 100 kVA pole mounted transformer design is especially effective for cost-efficient deployment in regions with low population density.

1.2 Technical Specification

100kVA single phase pole mounted transformer specification and data sheet

Delivered toGuyana
Year2025
TypeSingle phase pole mounted transformer
StandardIEEE & ANSI C57.12.00
Rated Power100KVA
Frequency60HZ
PolaritySubtractive
Vector groupIi0
Primary Voltage13800V
Secondary Voltage120/240V
Winding MaterialCOPPER
Impedance2%
Cooling MethodONAN
Tap ChangerNLTC
Tapping Range±2X2.5%(Total range=10%)
No Load Loss263W
On Load Loss1160W
AccessoriesStandard Configuration

 

1.3 Drawings

100kVA single phase pole mounted transformer dimensions and weight details

100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer with corrugated radiators drawing

02 Manufacturing

2.1 Core

In transformer manufacturing, the core plays a vital role as the main path for magnetic flux, directly affecting performance and efficiency. In the image, multiple rolled cores are neatly arranged after passing dimensional checks and positioning. Workers follow standardized procedures to ensure tight, aligned lamination, preparing the cores for precise coil assembly and the next stage of active part construction.100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer iron core

2.2 Winding

100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer windingsThe 100kVA single phase pole mounted transformer uses copper windings. The low voltage coil adopts foil winding with high-conductivity copper foil, wound tightly with layered insulation. The high voltage coil uses enamelled copper wire, precisely wound with insulation between layers. After winding, coils are vacuum dried and cured to enhance insulation strength and long-term reliability.

2.3 Tank

The mild steel oil tank, with corrugated radiators on both sides, undergoes careful quality checks before assembly. In the image, workers are performing dimensional checks by measuring key parts, conducting visual inspections to spot surface defects or weld issues, and verifying the surface treatment condition. These thorough checks ensure the oil tank meets the required standards for reliable transformer performance.100 kva 13.8 kv to 0.24kv 0.12kv dual secondary pole mounted transformer oil tanks

03 Testing

Routine Test

  1. Resistance Measurements
  2. Ratio Tests
  3. Polarity Test
  4. No Load Losses and No Load Current
  5. Load Losses and Impedance Voltage
  6. Applied Voltage Test
  7. Induced Voltage Withstand Test
  8. Insulation Resistance Measurement
  9. Oil Dielectric Test
  10. Leak Testing with Pressure for Liquid Immersed Transformers

Testing Standard

  • IEEE C57.12.20-2017
    IEEE Standard for Overhead-Type Distribution Transformers 500 kVA and Smaller; High Voltage, 34500 V and Below; Low Voltage, 7970/13 800Y V and Below
  • IEEE C57.12.90-2021
    IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
  • CSA C802.1-13 (R2022)
    Minimum Efficiency Values for Liquid-Filled Distribution Transformers

Test Results

No.Test ItemUnitAcceptance

Values

Measured ValuesConclusion
1Resistance Measurements///Pass
2Ratio Tests/The deviation of the voltage ratio on the principal tapping: ≤0.5%

Connection symbol: Ii0

-0.03Pass
3Polarity tests/SubtractiveSubtractivePass
4No-load losses and excitation current%

kW

I0 :: provide measured value

P0: provide measured value

the tolerance for no load loss is +10%

0.49

0.225

Pass
5Load losses , impedance voltage,total losses and efficiency/

kW

kW

t:85℃

Z%: measured value

Pk: measured value

Pt: measured value

the tolerance for impedance is ±10%

the tolerance for total load loss is +6%

2.33

0.857

1.082

99.17

Pass
6Applied Voltage Test/HV:34KV 60s

LV: 10kV 60s

No collapse of the test voltage occursPass
7Induced Voltage Withstand Test/Applied voltage (KV):

2 Ur

Duration(s): 48

Frequency (HZ): 150

No collapse of the test voltage occursPass
8Insulation Resistance MeasurementGΩHV-LV to Ground

LV-HV to Ground

HV&LV to Ground

35.9

17.4

16.2

Pass
9Leakage Test/Applied pressure:20kPA

Duration:12h

No leakage and no

Damage

Pass
10Oil Dielectric TestkV≥4556.41Pass

 

04 Packing and Shipping

05 Site And Summary

This 100kVA single-phase pole-mounted transformer is ideal for outdoor distribution in rural or suburban areas where a 13.8kV primary voltage steps down to 120/240V secondary voltage. Featuring copper windings, ONAN natural cooling, and a ±2×2.5% no-load tap changer, it offers high reliability and flexible voltage regulation-perfect for regions with voltage fluctuations or long-distance power delivery. Its compact design and easy pole mounting make it cost-effective for low-density population areas.

If your project requires:

• Low to medium capacity single-phase power

• Outdoor pole-mounted installation

• Stable voltage under fluctuating or extended distribution lines

• Efficient copper windings and natural cooling to reduce maintenance costs

This pole mounted transformer is an excellent fit. Contact us for more details and customization options.

Let's Discuss Your Needs and Find the Right Solution!